Standard IEC Ratings
From Open Electrical
Contents |
Introduction
Most IEC rated equipment have standard sizes that correspond to full sets or subsets of Renard numbers, especially from the four preferred series of Renard numbers outlined in ISO-3: R5, R10, R20 and R40.
Transformers
For transformer ratings under 10MVA, IEC 60076-1 suggest preferred values based on the R10 series: 10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80, 100, and multiples of 10n. For example, the preferred transformer sizes from 500kVA to 4000kVA are: 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000.
Motors and Generators
IEC 60072-1 Table 7 suggests the following preferred ratings (based on a subset of the R40 series) for motors (in KW) and generators (in kVA):
| 0.06 | 0.09 | 0.12 | 0.18 | 0.25 | 0.37 | 0.55 | 0.75 | 1.1 | 1.5 | 1.8* | 2.2 | 3* | 3.7 | 4* | 5.5 | 6.3* | 7.5 | 10* | 11 | 13* | 15 | 17* | 18.5 |
| 20* | 22 | 25* | 30 | 32* | 37 | 40* | 45 | 50* | 55 | 63* | 75 | 80* | 90 | 100* | 110 | 125* | 132 | 150 | 160 | 185 | 200 | 220 | 250 |
| 280 | 300 | 315 | 335 | 355 | 375 | 400 | 425 | 450 | 475 | 500 | 530 | 560 | 600 | 630 | 670 | 710 | 750 | 800 | 850 | 900 | 950 | 1000 |
(*) Note that these are "secondary series" ratings and are only to be used in cases of special need.
Cables
Standard cable sizes (in mm2) are as follows:
| 0.5 | 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 | 800 | 1000 |